FDA Adverse Event
Malfunction
Summary report: N
HILL-ROM NURSE CALL DATABASE SERVERS
MDR report key: 2143042
·
Received June 14, 2011
Report
- Report Number
- 2143042
- Event Type
- Malfunction
- Date Received
- June 14, 2011
- Date of Event
- May 27, 2011
- Report Date
- June 14, 2011
- Manufacturer
- HILL-ROM
- Product Code
- ILQ
- Product Problem
- Yes
- Report Source
- User Facility report
- Reporter Location
- UT, US
- Reporter Occupation
- RISK MANAGER
Narratives
Description of Event or Problem · 1
FAILURE OF RUBBER MOUNTS SECURING 4" BOX FAN, USED TO COOL THE RAID ARRAY DISK DRIVE, THIS FAILURE ALLOWS THE BOX FAN TO FALL FORWARD, SHORTING THE BOX FAN'S METAL FAN GRATE AGAINST THE RAID ARRAY CONTROLLER PCB. RESULTING IN AN ERROR OF "NO OPERATING SYSTEM FOUND" ON BOOT UP. OUR FACILITY HAS 11 OF THESE SERVES LOCATED IN DATA CLOSETS ACROSS THE CAMPUS. ALL 11 WERE INSTALLED IN 2007. OUR CLINICAL ENGINEERING TEAM IS IN THE PROCESS OF VISUALLY INSPECTING AND SECURING THE RUBBER FAN MOUNTS TO PREVENT ANY FUTURE FAILURES.
Devices
| Seq | Brand | Generic | Product Code | Manufacturer | Model | Lot | UDI-DI |
|---|---|---|---|---|---|---|---|
| 1 | HILL-ROM NURSE CALL DATABASE SERVERS | NURSE CALL DATABASE | ILQ | HILL-ROM | IBM MODEL X SERIES 226 | * |
Patients
| Seq | Age | Sex | Outcome | Treatment |
|---|---|---|---|---|
| 1 | * |